Schneider Electric SCADA Expert ClearSCADA Cross-site Scripting

Multiple cross-site scripting (XSS) vulnerabilities in Schneider Electric StruxureWare SCADA Expert ClearSCADA 2010 R3 through 2014 R1 allow remote authenticated users to inject arbitrary web script or HTML via unspecified vectors.

CVE 해결 방법

Schneider Electric advises all ClearSCADA users to take steps to secure the interfaces to the ClearSCADA system. The ClearSCADA database security configuration should be reviewed and updated to limit all system access to authorized users only. The access permissions of existing users should be reduced to only those required by their role (e.g., removing any higher level System Administration privileges from Operations or Engineering users), and specific accounts should be created with appropriate permissions for performing System Administration tasks. Existing ClearSCADA customers using WebX can protect their system from cross-site scripting attacks by disabling the “Allow database shutdown via WebX” option within the ClearSCADA Server Configuration utility. Existing ClearSCADA customers should take measures to ensure their system does not grant any system access until users have supplied a valid username and password. Schneider Electric has corrected the default user security permissions; however, upgrading an existing vulnerable installation to a new version will not affect existing configured database security permissions. Therefore, the measures suggested here are strongly recommended for all users. Schneider Electric has corrected these vulnerabilities in the following service packs: * ClearSCADA 2010 R3.2, Released October 2014, and * SCADA Expert ClearSCADA 2014 R1.1, Released October 2014. If asset owners wish to upgrade to a new ClearSCADA Service Pack, please contact the local Schneider Electric office for the latest software version for ClearSCADA; alternatively, these new versions are available for direct download from the Schneider Electric web site. To update their license (not required when upgrading to a service pack of the same version), asset owners are required to complete and submit an online form, which is available here: http://resourcecenter.controlmicrosystems.com/display/CS/StruxureWare+SCADA+Expert+ClearSCADA+Update... http://resourcecenter.controlmicrosystems.com/display/CS/StruxureWare+SCADA+Expert+ClearSCADA+Update+Request+Form New Service packs for ClearSCADA are available for download here: http://resourcecenter.controlmicrosystems.com/display/CS/SCADA+Expert+ClearSCADA+Support General instructions on how to upgrade the ClearSCADA license (if required) are available here: http://resourcecenter.controlmicrosystems.com/display/CS/Updating+Your+ClearSCADA+License

CVE 정보

관련 약점

CWE-ID 약점 이름 출처
CWE-79 Improper Neutralization of Input During Web Page Generation
The product does not neutralize or incorrectly neutralizes user-controllable input before it is placed in output that is used as a web page that is served to other users.

메트릭

메트릭 점수 심각도 CVSS 벡터 출처
V2 4.9 AV:N/AC:H/Au:S/C:N/I:N/A:C
V2 3.5 AV:N/AC:M/Au:S/C:N/I:P/A:N nvd@nist.gov

EPSS

EPSS는 취약점이 악용될 가능성을 예측하는 점수 모델입니다.

EPSS 점수

EPSS 모델은 0과 1(0~100%) 사이의 확률 점수를 생성합니다. 점수가 높을수록 취약점이 악용될 가능성이 높습니다.

EPSS 백분위수

백분위수는 EPSS 점수에 따라 CVE의 순위를 매기는 데 사용됩니다. 예를 들어 EPSS 점수 기준 95번째 백분위수의 CVE는 다른 CVE의 95%보다 악용될 가능성이 높습니다.

언급된 제품

구성 0

Aveva>>Clearscada >> Version 2010

Aveva>>Clearscada >> Version 2010

Aveva>>Clearscada >> Version 2013

Aveva>>Clearscada >> Version 2013

Aveva>>Clearscada >> Version 2013

Aveva>>Clearscada >> Version 2013

Aveva>>Clearscada >> Version 2013

Schneider-electric>>Scada_expert_clearscada >> Version 2013

Schneider-electric>>Scada_expert_clearscada >> Version 2014

참고 자료

https://ics-cert.us-cert.gov/advisories/ICSA-14-259-01
Tags : Third Party Advisory, US Government Resource