CVE ID | Published | Description | Score | Severity |
---|---|---|---|---|
Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU. | 7.5 |
High |
||
A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products. An attacker could exploit the vulnerability by using a specially crafted message sequence, to force the IEC 61850 MMS-server communication stack, to stop accepting new MMS-client connections. Already existing/established client-server connections are not affected. List of affected CPEs: * cpe:2.3:o:hitachienergy:fox61x_tego1:r15b08:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16_3:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1e01:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1d02:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1c07:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1b02:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:gms600:1.3.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.1.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.5.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.6.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.6.0.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.7.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.7.2:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.8.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.0.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.1.0.4:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.1.0.5:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.4:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.4.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:mms:2.2.3:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.2:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:reb500:7:*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:reb500:8:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:1.2.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:2.0.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:1.1.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:1.3.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:2.1.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:2.1.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relionSAM600-IO:2.2.1:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relionSAM600-IO:2.2.5:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:2.2.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:2.2.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:rtu500cmu:12.*.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:rtu500cmu:13.*.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:txpert_hub_coretec_4:2.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:txpert_hub_coretec_4:3.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:txpert_hub_coretec_5:3.0:*:*:*:*:*:*:* | 7.5 |
High |
||
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function. | 7.5 |
High |