Hitachi Energy Relion SAM600-IO Firmware 2.2.5

CPE Details

Hitachi Energy Relion SAM600-IO Firmware 2.2.5
2.2.5
2023-04-19
12h09 +00:00
2023-04-19
13h32 +00:00
Alerte pour un CPE
Restez informé de toutes modifications pour un CPE spécifique.
Gestion des notifications

CPE Name: cpe:2.3:o:hitachienergy:relion_sam600-io_firmware:2.2.5:*:*:*:*:*:*:*

Informations

Vendor

hitachienergy

Product

relion_sam600-io_firmware

Version

2.2.5

Related CVE

Open and find in CVE List

CVE ID Publié Description Score Gravité
CVE-2023-4518 2023-12-01 14h18 +00:00 A vulnerability exists in the input validation of the GOOSE messages where out of range values received and processed by the IED caused a reboot of the device. In order for an attacker to exploit the vulnerability, goose receiving blocks need to be configured.
7.5
Haute
CVE-2022-3353 2023-02-21 13h50 +00:00 A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products.  An attacker could exploit the vulnerability by using a specially crafted message sequence, to force the IEC 61850 MMS-server communication stack, to stop accepting new MMS-client connections.  Already existing/established client-server connections are not affected. List of affected CPEs: * cpe:2.3:o:hitachienergy:fox61x_tego1:r15b08:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16_3:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1e01:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1d02:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1c07:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1b02:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:gms600:1.3.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.1.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.5.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.6.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.6.0.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.7.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.7.2:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.8.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.0.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.1.0.4:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.1.0.5:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.4:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.4.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:mms:2.2.3:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.2:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:reb500:7:*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:reb500:8:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:1.2.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:2.0.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:1.1.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:1.3.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:2.1.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:2.1.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relionSAM600-IO:2.2.1:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relionSAM600-IO:2.2.5:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:2.2.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:2.2.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:rtu500cmu:12.*.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:rtu500cmu:13.*.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:txpert_hub_coretec_4:2.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:txpert_hub_coretec_4:3.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:txpert_hub_coretec_5:3.0:*:*:*:*:*:*:*
7.5
Haute
CVE-2021-35534 2021-11-18 16h35 +00:00 Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to an internal database tables, could allow anybody with user credentials to bypass security controls that is enforced by the product. Consequently, exploitation may lead to unauthorized modifications on data/firmware, and/or to permanently disabling the product. This issue affects: Hitachi Energy Relion 670 Series 2.0 all revisions; 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.5. Hitachi Energy Relion 670/650 Series 2.1 all revisions. 2.2.0 all revisions; 2.2.4 all revisions; Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions; 2.2.5 versions prior to 2.2.5.2. Hitachi Energy Relion 650 1.0 all revisions. 1.1 all revisions; 1.2 all revisions; 1.3 versions prior to 1.3.0.8; Hitachi Energy GMS600 1.3.0; 1.3.0.1; 1.2.0. Hitachi Energy PWC600 1.0.1 version 1.0.1.4 and prior versions; 1.1.0 version 1.1.0.1 and prior versions.
7.2
Haute